The base station climate control system is designed to maintain indoor temperature optimal for telecommunication equipment operation at the lowest possible power consumption. The BRKV-02 climate controller performs the process of automated control of the ventilation system and air conditioners. The BRKV controller is used to control uniform consumption of the mechanical resource of air conditioners and constant support of the required temperature by reducing the amount of energy consumption through cooling by external air and rotation with a specified time interval. When the air conditioner rotation and ventilation unit is operating, the reduction in energy consumption reaches 50% compared to facilities equipped with air conditioning systems only.
BRKV-02 Microclimate controller
- Operating Temperature, °C
- from -20 to +80
- Power supply from constant voltage source
- (18-72) V
- Power consumption
- 5 W (max)
- Tolerable absolute error of the controller clock in the operating temperature range
- ±1 s/day
- Temperature sensor measurement error (in the range of -10 +85°C)
- no more than ±0.5°C
- Journal volume
- Up to 1 year
- Number of digital inputs
- 6
- Number of relay outputs (250V, 150W)
- 4
- Number of relay outputs (250V, 50mA)
- 4
- Number of temperature sensors
- 3 pcs
- RS485 interface
- 1 pc.
- Number of IR sensors
- 2
- Air conditioner rotation time (adjustable)
- 1…255 hours
You can download the manual by clickinghere.